A camera for a Class I, Division 2 area has to be approved for that class, division and gas group, and its temperature rating has to stay below the ignition temperature of the gas or vapor on site. Start from the area classification document, then match the camera marking to it. Image quality and connectivity come after that.
This guide explains what Division 2 means, which protection methods are accepted there, and what to check before you buy.
What Class I Division 2 means
Class I covers locations where flammable gases or vapors may be present in the air. Division 2 is the part of that system where an ignitable mixture is not expected in normal operation. It appears only when something goes wrong.
Under the OSHA definition, a location is Class I, Division 2 when one of three conditions applies:
- Flammable liquids or gases are handled or processed, but they stay inside closed containers or systems and escape only through accidental rupture, breakdown or abnormal operation.
- Mechanical ventilation normally prevents an ignitable concentration, and the area could become hazardous if that ventilation fails.
- The location is next to a Division 1 area, and vapors could occasionally reach it.
Typical examples are the area around closed process piping with valves and flanges, pump and compressor buildings with forced ventilation, and the band that surrounds a Division 1 zone at a loading rack or tank vent.
Division 2 compared with Division 1
- When the hazard is present: in Division 1, in normal operation or often during maintenance and leaks. In Division 2, only under abnormal conditions.
- Rough zone comparison: Division 1 lines up with Zone 0 and Zone 1. Division 2 lines up with Zone 2.
- Protection methods accepted: Division 1 accepts a short list, such as explosionproof, intrinsically safe and purged. Division 2 accepts those methods plus methods made for Division 2, such as nonincendive.
- Typical equipment: Division 1 equipment is heavier and more costly. Division 2 offers a wider choice, often lighter.
The zone comparison is only a guide. A site is classified under one system or the other, and equipment has to carry the marking for the system the site uses.
How an area gets classified
The camera supplier does not classify the area. The facility owner does, normally through a qualified engineer who studies the materials handled, the release sources and the ventilation.
The result is an area classification drawing or document. OSHA requires classified areas to be documented, and that documentation has to be available to the people who design, install, inspect, maintain or operate electrical equipment there.
Ask for that document before you ask for a camera quote. It tells you four things you need:
- The class and division of the exact mounting point
- The gas group, such as Group D for propane and methane or Group B for hydrogen
- The required temperature class
- Where the boundaries are, so you know if the camera, the junction box and the cable route all sit in the same division
What equipment is accepted in Division 2
OSHA lists the protection techniques accepted for electrical equipment in hazardous locations. For Class I, Division 2, the list includes:
- Explosionproof apparatus, approved for the location
- Purged and pressurized enclosures, which keep the atmosphere out with clean air or inert gas
- Nonincendive circuits, equipment and components, which cannot ignite the atmosphere in normal operation
- Hermetically sealed devices, where the atmosphere cannot reach the arcing parts
Two more rules matter when you compare products:
- Equipment approved for a Division 1 location may be installed in a Division 2 location of the same class and group.
- General-purpose equipment is allowed in Division 2 only if the employer can demonstrate that it is not a source of ignition under normal operating conditions. For a camera with heaters, illuminators or a wireless radio, that is a hard case to make, so most sites require marked and approved equipment.
What to check on the camera
Marking and certificate
The nameplate should state the class, division, gas group and temperature class or operating temperature. Each of those has to match or exceed what the area document asks for.
Ask the supplier for the certificate from the testing laboratory, and check that the model and configuration on the certificate are the ones being quoted. A certificate for the housing alone does not cover a camera, heater or radio that was added later.
Gas group
Groups are not interchangeable. Equipment marked for Group D only is not acceptable where hydrogen is present. If the site handles more than one material, the equipment has to cover the most demanding group.
Temperature class and ambient range
The marked operating temperature must not exceed the ignition temperature of the gas or vapor present. Temperature classes run from T1 at 450 °C down to T6 at 85 °C, and the area document says which one applies.
Check the ambient range as well. Ratings are normally based on a 40 °C ambient, and equipment approved for hotter locations has to show that higher ambient on the marking. A camera in direct sun on a Gulf Coast pipe rack and a camera in a northern winter need different ranges.
Enclosure and environment
The hazardous location approval says nothing about rain, washdown or corrosion. Look for a separate enclosure rating such as Type 4X or IP66, and pick the housing material for the site. Coastal, offshore and chemical sites usually need stainless steel or a coated aluminum built for corrosive air.
Power and connectivity
Decide how the camera gets power and sends video before you choose the model: PoE, fiber through a media converter, or cellular where there is no network.
Every device inside the classified area counts, not only the camera. Junction boxes, switches, media converters and antennas need their own approval for the location. Wiring methods and conduit seals follow the electrical code and should be installed by people qualified for hazardous locations.
Imaging
Once the safety requirements are met, choose the camera for the job:
- Fixed cameras for a constant view of one asset, such as a flare stack, pump or gauge
- PTZ cameras for wide areas where an operator needs to look around
- Thermal imaging for leaks, hot spots and scenes with no light
- Resolution and low-light performance matched to the distance and the detail you need to read
Our guide to how explosion proof cameras work covers these camera types in more detail.
Using a Division 1 camera in a Division 2 area
Because Division 1 equipment is accepted in Division 2 for the same class and group, many sites standardize on Division 1 cameras for both. It costs more per camera, and it has practical advantages:
- Boundaries between divisions are not always obvious in the field, and a camera mounted a short distance from the drawing position may fall on the other side
- Areas get reclassified when a process changes
- One model across the site means one set of spares and one installation procedure
- Cameras can be moved between areas without a new approval question
A camera designed only for Division 2 is the lighter and less costly choice when the classification is stable and the boundaries are clear.
Spectrum’s fixed cameras and dome cameras are certified for Class I, Division 1 locations. The groups, temperature class and certificate numbers for each family are on the certifications page. Confirm any installation against your own area classification and the authority having jurisdiction.
Selection checklist
- Area classification document in hand for the exact mounting point
- Class, division and gas group on the camera marking match the document
- Temperature class is at or below the limit for the material present
- Ambient temperature range covers the site
- Certificate covers the quoted model and configuration
- Enclosure rating and material suit the weather and the chemicals on site
- Junction boxes, converters, antennas and other accessories are approved for the location
- Power and network path defined, with a qualified installer for wiring and seals
- Camera type, resolution and lens chosen for the task
If you want help matching a camera to your classification, request a quote and include the class, division, group and temperature class from your area document. Standard models with pricing are also available in our online store.
Questions about Class I Division 2 cameras
What is a Class I Division 2 location?
It is a location where flammable gases or vapors are handled but are not present in ignitable concentrations during normal operation. The hazard appears only under abnormal conditions, such as a leak, an equipment failure or a ventilation failure.
Can a Class I Division 1 camera be installed in a Division 2 area?
Yes. Equipment approved for a Division 1 location may be installed in a Division 2 location of the same class and group. The gas group and temperature class still have to match the area.
Do I need an explosion proof camera in Class I Division 2?
Not always. Explosionproof equipment is one accepted method. Nonincendive, purged and pressurized, and hermetically sealed equipment approved for Division 2 are also accepted. An ordinary camera with no hazardous location approval is very hard to justify.
Is Class I Division 2 the same as Zone 2?
They describe a similar level of risk, where the hazard is present only under abnormal conditions. They belong to different classification systems, so the equipment must carry the marking for the system your site uses.
Who decides whether an area is Division 1 or Division 2?
The facility owner, normally through a qualified engineer who studies the materials, the release sources and the ventilation. The result is recorded in an area classification document. A camera supplier does not classify the area.
What markings should a camera for Division 2 have?
The class, the division, the gas group and the temperature class or operating temperature, plus the mark of the testing laboratory. Ask for the certificate and check that it covers the exact model and configuration.